Ht-instruments HT9022 Bedienungsanleitung Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 56
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
HT9022
EN - 19
5.3.3. Checking phase sequence and phase concordance with a lead
WARNING
While measuring, the instrument must be held in the operator’s hand.
Press key F1 (Mod) to open the drop-down menu shown on the
screen to the side. At each subsequent pressure of key F1
(Mod), the cursor will scroll through the available items. Select
Ph Seq” and press key F4 (OK) to confirm the selected item.
Mod Par Ok
AC <10.0 Hz
---- V
19/01-17:00:00
5.3.3.1. Verification of Phase Sequence.
Fig. 7: verification of phase sequence
1. The instrument shows the screen here to the side, and waits
for the detection of phase L1.
2. Insert the red cable into input terminal V and connect the
red lead to phase L1 (Fig. 7).
Mod Go
Ph Seq
PH1
Wait
19/01-17:00:00
AC
DC
Ph Seq
Help
Esc
Seitenansicht 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 55 56

Kommentare zu diesen Handbüchern

Keine Kommentare