MACROTEST 5035
EN - 22
4.3.1.1. Mode "MAN x½"
4. Press the START/STOP key once. The instrument carries out the
test injecting a current in phase with positive half wave of the
voltage indicated on display by 0°.
Press the START/STOP key twice. The instrument carries out the
test injecting a current in phase with negative half wave of the
voltage indicated on display by 180°.
If the RCD does NOT trip the
instrument emits a double sound
signal indicating the positive
outcome of the test and displays the
screen alongside.
RCD ~
> 999 ms
OK
Ι
N
30mA 2 V
x1/2
MAN
U
L
= 50V
SAVING: The test can be stored pressing the SAVE key twice
(according to paragraph 5.1).
Value of contact
voltage U
t
detected referred
to the rated value
of the RCD
current set.
OK: indicates that
RCD passed the
test.
The symbol ">" means that the RCD did not trip.
Indicates if the test was carried out with current
phase 0° or 180° with respect to the voltage.
or RCD
SAVE
START
STOP
Limit set for the
co
n
tac
t
v
o
l
tage