FULLTEST 3
EN - 31
5.5.3. RCD MEASUREMENT
Measured quantities and display ranges:
Trip out time at IN/2 0 1000 ms (AC, A, B, general, selective, delayed)
Trip out time at IN 0 1000 ms (AC, A, B, general, selective, delayed)
Trip out time at 2IN 0 200 ms (AC, A, general), 0 250 ms (AC, A, selective)
Trip out time at 4IN 0 200 ms (B, general), 0 250 ms (B, selective)
Trip out time at 5IN 0 50 ms (AC, A, general), 0 150 ms (AC, A, selective)
AUTO test YES (general, selective)
Trip out current (Ramp test) 10 110% of IN in steps of 5% of IN (general)
Input requirements:
Mains voltage UL/N (READY condition) 100 265 V AC
Mains voltage U
L/PE (READY condition) 100 265 V AC
1) Select the RCD function by pressing the FUNC hard key first.
2) Check selected RCD type (AC, A or B) and selected characteristic (GENERAL, SELECTIVE or
DELAYED) and modify it if needed by pressing the TYPE (5) touch-screen key first. If DELAYED
characteristic is selected, the screen will turn to delay time adjustment mode automatically.
3) Select nominal differential current by pressing the IN touch-screen key first.
4) Select wished measurement by pressing the MEAS touch-screen key first (t/1/2IN, t/IN, t/2IN,
t/5IN, I or AUTO).
5) Check selected polarity and modify it if needed by pressing the POL (8) touch-screen key first.
6) Select measurement screen by pressing the (4) touch-screen key and check all settings again.
7) Connect the test leads according to one of the figures below.
Figure 20: Connection of schuko test cable
Figure 21: Connection of test leads